Permit: T12CM07493

Parcel: 134232920


Addresses:

6434 E SCARLETT ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/15/2013 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
01/09/2013 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
12/27/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
MAX #15 GAGE MAY BE USED WITH A 10 PSI TEST. GAGE SHALL HAVE 1/10 THE PSI INCREMENTATION. PROVIDE INFORMATION REQUESTED. COMPLETE NOTED CORRECTIONS.
12/19/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE PROVIDE THE INSULATION MANUAL FOR YOUR WATER HEATER. ALSO PROVIDE DATA PLATE INFORMATION, OR REPOSITION HEATER WITH PLATE VISIBLE. 1/2" PIPING IS UNDERSIZED FOR 100000 BTU @ 40' DEVELOPED LENGTH, PROVIDE A DEDICATEDD GAS SUPPLY SIZED PROPERLY FOR UNIT. A TEST IS REQUIRED FOR NEW PIPING. FRONT OF HEATER REQUIRES ACCESS. COMPLETE NOTED CORRECTIONS
12/17/2012 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*