Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM07485
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2013 | FIRE - FINAL | Approved | ||
01/22/2013 | FIRE - FINAL | Partial Approval | TEMP C OF O APPROVED to get final need approved plan and permit for sprinkler work that was done, cover 4 sq elect. baox above drop ciling and cover by duct work to attic in the interstitail space. | |
01/14/2013 | FIRE - FINAL | Denied | 1. Need separate plan and permit for any added and relocated sprinkler heads 2. Front exit doors need to be corrected as per IFC 1008.1.9 "Panic & Fire hardware" 2006 ed. Double doors can not use slide bolt locks must be spring loaded flush bolt locks that open and close all by themselves. 3. Need to sprinkler the interstitial space above drop ceiling because it has combustible materials and holes to the attic space or keep it non-combustible and cover all holes in old ceiling with non-combustible materials. |