Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM07485

Parcel: 12809006B


Addresses:

5443 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM07485

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2013 FIRE - FINAL Approved
01/22/2013 FIRE - FINAL Partial Approval TEMP C OF O APPROVED to get final need approved plan and permit for sprinkler work that was done, cover 4 sq elect. baox above drop ciling and cover by duct work to attic in the interstitail space.
01/14/2013 FIRE - FINAL Denied 1. Need separate plan and permit for any added and relocated sprinkler heads
2. Front exit doors need to be corrected as per IFC 1008.1.9 "Panic & Fire hardware" 2006 ed. Double doors can not use slide bolt locks must be spring loaded flush bolt locks that open and close all by themselves.
3. Need to sprinkler the interstitial space above drop ceiling because it has combustible materials and holes to the attic space or keep it non-combustible and cover all holes in old ceiling with non-combustible materials.