Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12CM07485
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2013 | FIRE SPKLR - FINAL | Approved | ||
01/14/2013 | FIRE SPKLR - FINAL | Denied | 1. Need separate plan and permit for any added and relocated sprinkler heads 2. Front exit doors need to be corrected as per IFC 1008.1.9 "Panic & Fire hardware" 2006 ed. Double doors can not use slide bolt locks must be spring loaded flush bolt locks that open and close all by themselves. 3. Need to sprinkler the interstitial space above drop ceiling because it has combustible materials and holes to the attic space or keep it non-combustible and cover all holes in old ceiling with non-combustible materials. |