Permit: T12CM07456

Parcel: 127041780


Addresses:

4913 E 4TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/23/2013 PLUMBING - FINAL Approved IVRS - Inspection :*
05/03/2013 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/03/2013 PLUMBING - FINAL Denied DO NOT USE BLACK IRON PIPE IN THE T & P DRAIN. YOU CANNOT HAVE FLEX COPPER IN A T & P DRAIN. PROVIDE A 90 DEGREE ELBOW WHERE T & P DRAIN TERMINATES. REMOVE ALL FOIL TAPE FROM VENT PIPING. IT APPEARS SOME OF THE VENT MAY BE UPSIDE DOWN, MAYBE MIX MATCHED PIECES FROM DIFFERENT MANUFACTURERS. THERE NEEDS TO BE MIN 1" CLEARANCE FROM COMBUSTIBLES AT PENETRATION THROUGH ROOF. THE VENT NEEDS TO EXTEND ABOVE THE UPPER ROOF & WITH AN APPROVED CAP. PROVIDE ACCESS TO ROOF.
PROVIDE COMBUSTION AIR INTO THE ENCLOSURE. THE GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH. THE T & P DRAIN MUST SLOPE DOWNHILL THE ENTIRE WAY.
03/07/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* SORRY, THE MESSAGE COMPUTER IS DOWN TODAY AND WE CAN'T RETRIEVE OUR MESSAGES. PLEASE RECALL. THANKS