Permit: T12CM07432

Parcel: 13414001K

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12CM07432

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2013 FIRE SPKLR - FINAL Approved
01/26/2013 FIRE SPKLR - FINAL Partial Approval Repair or replace flow switch on main riser failed to work
01/24/2013 FIRE SPKLR - FINAL Partial Approval Trouble with pre-action, clean agent not ready. Pre-action as of today is a wet system until problems ar corrected
01/23/2013 FIRE SPKLR - FINAL Cancelled Still need Pre-action done
01/16/2013 FIRE SPKLR - FINAL Partial Approval Add coverage in elevator pit
Move horn/strobe away from side wall sprinkler in south stairwell 2nd floor.
Install pre-action system completely.
Wire sprinkler system to new fire alarm panel