Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2013 | FIRE SPKLR - FINAL | Approved | ||
| 01/26/2013 | FIRE SPKLR - FINAL | Partial Approval | Repair or replace flow switch on main riser failed to work | |
| 01/24/2013 | FIRE SPKLR - FINAL | Partial Approval | Trouble with pre-action, clean agent not ready. Pre-action as of today is a wet system until problems ar corrected | |
| 01/23/2013 | FIRE SPKLR - FINAL | Cancelled | Still need Pre-action done | |
| 01/16/2013 | FIRE SPKLR - FINAL | Partial Approval | Add coverage in elevator pit Move horn/strobe away from side wall sprinkler in south stairwell 2nd floor. Install pre-action system completely. Wire sprinkler system to new fire alarm panel |