Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T12CM07398

Parcel: 141186320


Addresses:

9260 S HOUGHTON RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/11/2014 FIRE - ALARM FINAL Approved
01/16/2014 FIRE - ALARM FINAL Partial Approval 1. Tested the following to finish the alarm system final:
a. Water flow - Passed
b. Sprinkler bell - Passed
c. Commercal Hood - Passed
Tested duct smokes:
RTU -1 - Passed
RTU-4 - Passed
RTU -8 - Passed
RTU-9 - Failed bad transformer for smoke
RTU-10 - Passed
RTU-11 - Passed
RTU- 12- Passed
RTU-13 - Passed
RTU-18 - Passed
AHU-1 - Passed
AHU-2 - Failed bad duct smoke detector
Will re-test the failed sections