Permit: T12CM07398

Parcel: 141186320


Addresses:

9260 S HOUGHTON RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
02/11/2014 FIRE SPKLR - FINAL Approved
01/16/2014 FIRE SPKLR - FINAL Partial Approval 1. Need fire final test results & factory pump test results
2. Label fire riser door "FIRE RISER ROOM"
3. Correct sprinkler coverage in the freezer room west side 4th one, blocked by lights
4. Sign pump test header
5. Sign all valves in fire pump room and all auxiliary drain valves on sprinkler system