Permit: T12CM07366

Parcel: 122121270

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Permit Number - T12CM07366

Inspection Description - PLUMBING - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
11/26/2012 PLUMBING - FINAL Partial Approval SHOULD HAVE BEEN PARTIAL DUE TO NOTED NEEDED PRIOR TO SCHEDULING FINAL
11/23/2012 PLUMBING - FINAL Approved PROVIDE A NEW T+P RELIEF VALVE PROVIDE MIN 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS
PROVIDE AN ELETRICAL BOND TO GOT PIPING
EXTEND FURNACE/WATER HEATER VENT 3' ABOVE EVAP COOLER
15 PSI TEST IS OK
LEFT GAS CARD
RECALL FOR FINAL
11/21/2012 PLUMBING - FINAL Partial Approval IVRS - Inspection :*