Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/24/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/21/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PREVIOUS INSPECTION WRITE UPS TO BE OUTSIDE. 2. GROUNDING ELECTRODE CONDUCTOR TO BE BONDED ALL ENDS OF RACE WAYS 250.64 3. NEED LABELING PER 690.17 ON COMBINER PANEL. 4. PLEASE PROVIDE OSHA APPROVED LADDER FOR ROOF ACCESS. 5. PROVIDE APPROVED AND LISTED GROUNDING LUGS & JUMPER STRAPS PER 690.41 -43 6. INSTALL MOUNTING LEGS PER UNIRAC INSTRUCTIONS. 7. PROVIDE PHYSICAL PROTECTION FOR 8V CONDUCTORS. 8. CLEAN SURFACE UNDER LUG & USE APPROVED HARDWARE 250.8 &250.12 9. LABEL BREAKERS 408.4 10. NEED AN APPROVED & LISTED JUNCTION BOX AT 2ND STRUCTURE |