Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T12CM07068
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
11/13/2012 | PLUMBING - FINAL | Not ready for Inspection | 1. Label electrical box. 2. At water heater- black iron pipe is not approved for potable water. Require sediment trap. Vent not properly connected. Vent to extend a minimum of five feet above the water heater.. Tand P relief drain may not have backpitch. | |
11/07/2012 | PLUMBING - FINAL | Not ready for Inspection | 1. GATES LOCKED-NO ACCESS. NUMBER LEFT NO LONGER IN SERVICE. |