Permit: T12CM07012

Parcel: 13623009B

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T12CM07012

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/25/2013 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
03/19/2013 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*OK TO COVER SEWER PROVIDE REV
03/14/2013 PLUMBING - SEWER HCS CONNECT Denied 4" CO REQ TO SERVCE 4" SEWER CORRECT SLOPE REMOVE ROCKS AND DEVRIS SHADS WITH CLEAN FILL, REVISION REQ FOR FINAL
01/22/2013 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*9AM PRECON W/ GEE FROM BARKER M. MIKE W/ UTILITY UNDERGROUND AND LANCE W/ WOOD PATCH ENGINEERING. PROVIDE A CITY APPROVED PLAN AND PERMIT. SEE ROBERT SHERRY. ENGINEER CHANGES MAY BE RED LINED ON A CITY APP PLAN W/ REVISIONS TO FOLLOW. PRIVATE SERVICE REQUIRING ADEQ AUTHORIZATION PRIOR TO ANY DISCHARGE. CALL FOR DAILY INSPECTIONS. WILL AIR TEST LATER AT OWN RISK. DIRECTIONAL FITTINGS AND TRACER WIRE REQUIRED.