Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/15/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/15/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1. PROVIDE BOND GAS & WATER 2. CLAMP RISER 3. PROVIDE METAL ADDRESS TAG 4. SECURE #4 TO BUILDING |
|
| 04/12/2013 | ELECTRIC - SERVICE UPGRADE | Denied | NO RECORD OF UFER INSPECTION NEED TO BOND WATER /GAS PIPING GROUND RODS MUST BE COMPLETELY IN GROUN 2 REQUIRED 6' APAART DO NOT BEND GROUND ROD PLUG HOLES IN BACK OF PANEL WITH FIRE RATED MATERIAL BOND BUSHINGS REQUIRED AT RISER CONDUIT |
|
| 04/10/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/05/2013 | ELECTRIC - SERVICE UPGRADE | Partial Approval | -OK U.G CONDUIT -SERVICE PANEL MISSING GROUNDING ELECTRODE SYSTEM |