Permit: T12CM06989

Parcel: 12703448D


Addresses:

801 N SAHUARA AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/07/2013 BUILDING - FINAL Approved IVRS - Inspection :*
01/11/2013 BUILDING - FINAL Denied service is split buss panel. the buss tied into is only rated for 60 amps. you can go 120 % which equals 72 amps. the main breaker which is 60 amp plus 35 amp pv breaker= 95 amp. russ is too small any questions call Ray Majuta at City Of Tucson 520-9609-4891.
Open DC meter and inverter for inspection provide a roof jack at elec penetration through roof
secure 2 DC cables dangling below solar panels