Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2013 | BUILDING - FINAL | Denied | service is split buss panel. the buss tied into is only rated for 60 amps. you can go 120 % which equals 72 amps. the main breaker which is 60 amp plus 35 amp pv breaker= 95 amp. russ is too small any questions call Ray Majuta at City Of Tucson 520-9609-4891. Open DC meter and inverter for inspection provide a roof jack at elec penetration through roof secure 2 DC cables dangling below solar panels |