Permit: T12CM06955

Parcel: 13005283A


Addresses:

2037 E 34TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2012 ELECTRIC - FINAL Denied 1. FRONT PORCH LIGHT MISSING SAFETY GLOBE
2. REAR POTCH LIGHT NOT INSTALLED PER CODE, PROVIDE ENCLOSURE PORCH LIGHT NOT INSTALLED TO WOOD SURFACE
3. SERVICE PANEL IS TO HAVE ADDRESS LABELED WITH U.V RESISTANT LABELING
4. ELETRICAL OUTLET IN FURNACE CLOSET IN DISREPAIR OR BROKEN
5. OUTLETS IN BEDROOM BROKEN OR IN DISPREPAIR
6. THIS IS AN UNDERGROUND ELETRICAL SYSTEM, REMOVE ALL GROUNDED OUTLETS (EXCEPT GFCI) AND REPLACE WITH UNGROUNDED OUTLETS
7. SMOKE ALARM REQUIRED IN HALLWAY