Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2012 | EXCAVATION/LAYOUT REBAR & ZON | Approved | OK PER BUILDING FINAL | |
| 11/15/2012 | EXCAVATION/LAYOUT REBAR & ZON | Denied | 1 EXPOSE FOOTERS TO VERIFY DEPTH PER DETAIL 1/4 2. 2X6 RAFTERS INSTALLED IN LIEU OF 2X12 RAFTERS PER ROOF FRAMING PLAN 3. MISSING WALL MOUNTED A/C HEAT UNIT 4. EXPOSE RAFTER SO WALL CONNECTIONS PER DETAIL 5/4 5. SHER WALLS 5/8 SIDING IN LIEU OF 3/8" OSB 6. STOOP EXIT DOORS 7. REMOVE FILL EXT DIRT FROM SIDING 8. SMOKE ALARMS PER CODE & PLAN CIRCUIT 22 9. PROVIDE CLEARANCE PER CODE AT METER 10. PROVIDE LETTERHEAD LICENSED ELEC CONTRACTOR OR EXPOSE ALL ELEC 9. |
|
| 11/14/2012 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* |