Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T12CM06922
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2013 | PLUMBING - GAS PRESSURE TEST | Approved | ||
12/05/2012 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | 1. New gas pipe covered without inspection. Use correct gauge, fifteen pound gauge in 1/10 th pound incrementation. Test to ten pounds. There is no key inside the lockbox. No entry made. |