Permit: T12CM06910

Parcel: 120084100


Addresses:

161 W TENNESSEE ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/04/2012 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
11/21/2012 MECHANICAL - INTERMEDIATE Not ready for Inspection 1. CONDENSATE IS TO BE BLOCKED UP OFF ROOF A MIN OF 1.5" PVC IS TO BE BE COATED FOR U.V PROTECTION WHERE EXPOSED TO DAYLGHT ALL ROOF PENETRATIONS REQUIRE ROOF JACKS
2. ITEMS 1.3.4 DATED 11-14-12 HAVE BEEN CORRECTED
11/14/2012 MECHANICAL - INTERMEDIATE Partial Approval 1.PROVIDE PROPER CLEARANCE FROM FLUE PIPE TO COMBUSTIBLES ON WATER HEATER
2. CONDENSATE NOT INSTALLED TERMINATE 6" ABOVE GRADE
3. NEUTRAL WIRE NOT TO BE USED AS HOT LEG
4. PROVIDE SEDIMENT TRAP AT GAS LINE TO UNIT