Permit: T12CM06867

Parcel: 127122240


Addresses:

5708 E BURNS ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/16/2012 MECHANICAL - FINAL Partial Approval MINI SPLIT CONDENSOR OVERFUSED 15 AMPS IS MAX.
DO NOT USE PLASTIC DRAIN HOSE OUTDOORS SECURE MINI SPLIT CONDENSOR TO BASE DO NOT USE WHITE WIRE FOR HIGH VOLTAGE AT MINI SPLIT CONDENSOR
PROTECT ALL SECTIONS OF ARM FLEX AT TRANE CONDENSOR