Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/13/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #8 ROMEX TO SMALL FOR 100 AMP CIRCUIT BREAKER. OLD EXISTING INDOOR BREAKER BOX NOT APPROVED AS J-BOX OUTSIDE, USE NEMA3 BOX. |
|
| 10/30/2012 | ELECTRIC - FINAL | Denied | 1. BOND WATER AND GAS PIPING 2. USE A LISTED RISER CONDUIT BRACE- HOME MADE OUT OF EMT CONDUIT NOT APPROVED 3. OK GROUND RODS |