Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM06834
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2013 | FIRE - FINAL | Approved | ||
03/26/2013 | FIRE - FINAL | Denied | 1. Need address numbers posted on building (like 7932 - 7952 or 7932 - 52), post on front of building facing Broadway 12" high letters. (Handout given) 2. Need annual fire sprinkler inspection done 3. Need 5 year check valve inspection done. 4. Fire department connection (FDC) blocked by a storage cabinet keep 36" inched away 5. Install a sign over the FDC with 6" inch red letters on a white background stating "FDC". |