Permit: T12CM06795

Parcel: 133452040


Addresses:

335 N DIJON CT

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/04/2012 BUILDING - FINAL Approved IVRS - Inspection :*
11/29/2012 BUILDING - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
11/26/2012 BUILDING - FINAL Denied 1) PROVIDE PHYSICAL PROTECTION AND SUPPORT FOR PV AND GROUNDING CONDUCTORS
2) GROUND JUNCTION BOX
3) PLEASE PROVIDE INSTRUCTIONS FOR RAILS AND USE APPROVED PARTS SERVICE: WITH LISTED WBBB SYSTEMS 690.41 + 43
4) NEED LABELING ON ALL DISCONNECTING MEANS PER 690.17
5) MAINTAIN SAFE WORKING SPACE IN FRONT OF EQUIPMENT 110.26
6) GROUNDING ELECTRODE CONDUCTOR TO BE CONDNIOOS 250.64