Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/29/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 11/26/2012 | BUILDING - FINAL | Denied | 1) PROVIDE PHYSICAL PROTECTION AND SUPPORT FOR PV AND GROUNDING CONDUCTORS 2) GROUND JUNCTION BOX 3) PLEASE PROVIDE INSTRUCTIONS FOR RAILS AND USE APPROVED PARTS SERVICE: WITH LISTED WBBB SYSTEMS 690.41 + 43 4) NEED LABELING ON ALL DISCONNECTING MEANS PER 690.17 5) MAINTAIN SAFE WORKING SPACE IN FRONT OF EQUIPMENT 110.26 6) GROUNDING ELECTRODE CONDUCTOR TO BE CONDNIOOS 250.64 |