Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM06790
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2013 | FIRE - FINAL | Approved | ||
11/07/2013 | FIRE - FINAL | Denied | Need a sign above the fire department connections located on the southeast wall the sign shall have 6" inch red letters printed on a white background stating "FDC". Shall mount sign high as possible to see from Wilmot road. Need battery backup lighting install in new patio to meet exiting requirements. Need to add sprinkler coverage in the outside patio area and correct coverage on the soffit eastside dinning area. Need approved plans on site. |