Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2012 | ELECTRIC - FINAL | Approved | BACK FED 50 AMP PANEL PREDATES 1990 NEC REQUIREMENT FOR ADDITIONAL HOLD-DOWN SUPPLY BREAKER. OTHER ITEMS CORRECTED | |
| 10/29/2012 | ELECTRIC - FINAL | Partial Approval | 1. REDUCING WASHER IMPROPERLY INSTALLED 2. INSTALL ALL STRANDS UNDER TERMINAL CONNECTION 3. GROUNDING ELECTRODE CONDUCTOR NOT USE CAN AS BOND METHOD FOR NEUTRAL 4. BACK FED BREAKER TO HAVE MANUFACTURERS HOLD DOWN MAN BREAKER |
|
| 10/26/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |