Permit: T12CM06502

Parcel: 108160070


Addresses:

4810 N 1ST AV

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/12/2013 FIRE SPKLR - FINAL Approved
04/11/2013 FIRE SPKLR - FINAL Partial Approval Need pressure relief valve installed
Need cal plate installed
Remove cover plate on sprinkler head in driveway
Need tamper and flow switch monitored
Need Hood system monitored