Inspection History: FIRE SPKLR - FINAL

Permit Number - T12CM06483

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2013 FIRE SPKLR - FINAL Approved
09/09/2013 FIRE SPKLR - FINAL Partial Approval Install FD key box on riser door.
08/26/2013 FIRE SPKLR - FINAL Partial Approval 1. Label door on riser room with the following: "RISER ROOM"
2. Install FD key box on riser room door.
08/22/2013 FIRE SPKLR - FINAL Denied 1. No bell for sprinkler system need to install
2. Room #2 sprinkler head problem in the hot water heater room - check room again
3. Room #3 Upright by front t door needs to be 12" from deck. Check Kitchen and in closet. - check room again
4. Room #5 sprinkler head taped in closet - check room again
5. Room #7 Check for taped head - check room again
6. Room #9 Check sprinklers in closets - check room again
7. Signs need on the inspectors test valve and on riser
8. Need riser room door labeled "RISER ROOM"
9. Still need flow test and flow readings
10. Need Fire Dept. key box installed on riser room door for access.
11. Need Fire Dept. key access for main gates and access gate