Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T12CM06483
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2013 | FIRE SPKLR - FINAL | Approved | ||
09/09/2013 | FIRE SPKLR - FINAL | Partial Approval | Install FD key box on riser door. | |
08/26/2013 | FIRE SPKLR - FINAL | Partial Approval | 1. Label door on riser room with the following: "RISER ROOM" 2. Install FD key box on riser room door. |
|
08/22/2013 | FIRE SPKLR - FINAL | Denied | 1. No bell for sprinkler system need to install 2. Room #2 sprinkler head problem in the hot water heater room - check room again 3. Room #3 Upright by front t door needs to be 12" from deck. Check Kitchen and in closet. - check room again 4. Room #5 sprinkler head taped in closet - check room again 5. Room #7 Check for taped head - check room again 6. Room #9 Check sprinklers in closets - check room again 7. Signs need on the inspectors test valve and on riser 8. Need riser room door labeled "RISER ROOM" 9. Still need flow test and flow readings 10. Need Fire Dept. key box installed on riser room door for access. 11. Need Fire Dept. key access for main gates and access gate |