Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2013 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/08/2013 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/04/2013 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. nail protect plumbing 2. no water test ABS or potable water 3. nail protect home runs upstairs west bedroom closet 4. damaged fireblock mech room 5. shim bearing headers 6. R-6 installed in lieu of R-8 insulation to go below root sheating |