Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM06369
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2013 | FIRE - FINAL | Approved | ||
03/20/2013 | FIRE - FINAL | Denied | All egress doors for the 1st floor have a panic hardware device operation to them, Under the City of Tucson IFC Modifications section 1030.10 where panic hardware and fire exit hardware is installed within the required path of egress or any accessible to the public, there shall be no other locking device on the door. Fire alarm system is not needed for 1st floor at this time according to IFC 907.2.2 combined Group B load for all floors is 500 or more or occupant load is more than 100 persons above or below the lowest level of exit discharge. You can use the first floor only at this time, but when going for the C of O final for the 2nd floor a completely fully operational fire alarm system that meets the IFC 907 and the NFPA 72 standards will be needed. |