Permit: T12CM06150

Parcel: 127031950


Addresses:

5702 E 2ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM06150

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/04/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSED NM CABLE ON INTERIOR
2) GROUNDED RECEPTACLES ON NON GROUNDED WIRING
3) KITCHEN RECEPTACLES REPLACED- NEED TO BE GFCI PROTECTED
4) SMOKE DETECTORS NEEDED IN ADDITION BEDROOM AND OUTSIDE OF BEDROOM
5) OUT DOOR RECEPTACLES NOT FOR WET LOCATION (ROOF ALSO)
6) NEW BREAKER MARKED A/C TO BE LISTED FOR USE BY MANUFACTURE
7) POOL EQUIPMENT WIRING IN DETERIORATED AND MISSING CONDITIONS NON CODE COMPLIANT
8) CARPORT WIRING NON CODE COMPLIANT
*WATER HEATER FUSE SEPERATED