Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/27/2012 | BUILDING - FINAL | Denied | 1. MAINTAIN WORKING SPACE IN FRONT OF A/C DISCONNECT 110.26 2. NEED LABELING ON INVERTER 690.17 3. SEAL ROOF JACK FOR SERVICE 4. TIGHTEN LOOSE FITTINGS 5. SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 6. PLEASE VERIFY GAS BOND. * CALL MARK- SOLAR CITY- SOMEONE WAS SUPPOSE TO MEET INSPECTOR WAS ON SITE 40 MINS NO ONE SHOWED UP. |