Permit: T12CM06066

Parcel: 107040130

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/31/2012 FIRE - FINAL Approved
10/29/2012 FIRE - FINAL Denied Manager Danny 591-7760
1.) Original approved plans dated 03/2000 show that a monitoring system was to be installed for any sprinkler system that has more than 100 heads the approved plans show 144 heads. Therefore you will need to install a UL/FM approved fire alarm system for monitoring the water flow and tamper 24 hours a day 365. Will need an approved plan and permit for this work.
2.) Need to correct sprinkler coverage in track area next to 90 deg. elbow duct work.
10/23/2012 FIRE - FINAL Not ready for Inspection 1. heads need excussions and all painting needs to be complete before final will be given.
10/16/2012 FIRE - FINAL Not ready for Inspection 1. Extinguisher needs to be serviced.
2. Electrical work needs to be finished.