Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2012 | FIRE - FINAL | Approved | ||
| 10/29/2012 | FIRE - FINAL | Denied | Manager Danny 591-7760 1.) Original approved plans dated 03/2000 show that a monitoring system was to be installed for any sprinkler system that has more than 100 heads the approved plans show 144 heads. Therefore you will need to install a UL/FM approved fire alarm system for monitoring the water flow and tamper 24 hours a day 365. Will need an approved plan and permit for this work. 2.) Need to correct sprinkler coverage in track area next to 90 deg. elbow duct work. |
|
| 10/23/2012 | FIRE - FINAL | Not ready for Inspection | 1. heads need excussions and all painting needs to be complete before final will be given. | |
| 10/16/2012 | FIRE - FINAL | Not ready for Inspection | 1. Extinguisher needs to be serviced. 2. Electrical work needs to be finished. |