Permit: T12CM06066

Parcel: 107040130

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
10/31/2012 FIRE - ALARM FINAL Approved Feild notice given to Danny for the re-install of the monitoring system for the sprinkler tamper and flow switch so that we can clear this permit out.
10/29/2012 FIRE - ALARM FINAL Denied Original approved plans dated 03/2000 show that a monitoring system was to be installed for any sprinkler system that has more than 100 heads the approved plans show 144 heads. Therefore you will need to install a UL/FM approved fire alarm system for monitoring the water flow and tamper 24 hours a day 365. Will need an approved plan and permit for this work.