Permit: T12CM06059

Parcel: 138051060

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/14/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/30/2012 ELECTRIC - SERVICE UPGRADE Denied -2 GROUND RODS 6' APART, BOND GAS PIPE
-YOU CAN NOT RUN BOLT THRU RISER CONDUIT FOR RISER SUPPORT- USE A LISTED RISER SUPPORT
- I.D CIRCUIT BRKRS
10/17/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection WEAHTER HEAD NOT INSTALLED PER T.E.P REQUIREMENTS
ROOF JACK REQUIRED FOR ALL ROOF PENETRATION THIS IS NOT A COMPLETELIST