Permit: T12CM05876

Parcel: 125040120


Addresses:

2427 E 1ST ST

Inspection Status: Not ready for Inspection

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/06/2013 BUILDING - FINAL Not ready for Inspection 1. Finish cleanout between water closet and bathtub. Show how upstairs 1/2 bath has a GFCI circuit. T and P relief drain to be of approved material.
08/06/2013 BUILDING - FINAL Approved IVRS - Inspection :*
07/30/2013 BUILDING - FINAL Not ready for Inspection 1. 3/4" PEX yardwater to have 12" of cover at all points. Require blue tracer wire. No access to roof. Roof mounted tankless water heater- does manufacturer require any type of enclosure or protection? Note: PEX not to be installed in exterior exposed locations. Exterior piping on the roof to be protected. Armaflex to be made U.V. resistant. (Taping not permitted) Redline all changes to the plan. Hose bibbs to have vacuum breakers. Where is GFCI circuit at upstairs bathroom. Check roof flashings for leaks. Make cleanout accessible between the bathtub and the water closet in the upstairs bathroom.
03/18/2013 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*IM SORRY I NEGLECTED TO CALL FIRST, WATER HEATER SITTING OUTSIDE, WITH NO VENT. NO T AND P RELIEF, NO ENCLOSURE, WITH UNAPPROVED MATERIAL NOT ACCEPTED