Inspection Status: Not ready for Inspection
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2013 |
BUILDING - FINAL |
|
Not ready for Inspection |
1. Finish cleanout between water closet and bathtub. Show how upstairs 1/2 bath has a GFCI circuit. T and P relief drain to be of approved material. |
| 08/06/2013 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/30/2013 |
BUILDING - FINAL |
|
Not ready for Inspection |
1. 3/4" PEX yardwater to have 12" of cover at all points. Require blue tracer wire. No access to roof. Roof mounted tankless water heater- does manufacturer require any type of enclosure or protection? Note: PEX not to be installed in exterior exposed locations. Exterior piping on the roof to be protected. Armaflex to be made U.V. resistant. (Taping not permitted) Redline all changes to the plan. Hose bibbs to have vacuum breakers. Where is GFCI circuit at upstairs bathroom. Check roof flashings for leaks. Make cleanout accessible between the bathtub and the water closet in the upstairs bathroom. |
| 03/18/2013 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*IM SORRY I NEGLECTED TO CALL FIRST, WATER HEATER SITTING OUTSIDE, WITH NO VENT. NO T AND P RELIEF, NO ENCLOSURE, WITH UNAPPROVED MATERIAL NOT ACCEPTED |