Permit: T12CM05844

Parcel: 11005014C


Addresses:

2930 N SWAN RD #211

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/08/2013 FIRE - FINAL Approved
03/05/2013 FIRE - FINAL Denied 1. Fill in pocket ceiling with insulation or install sprinkler coverage or change all upright heads to QR type heads in the shell to meet open pocket ceiling requirements. (Pocket size 25' long x 31" deep x 3' wide).
2. Install suite numbers on door.