| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2013 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/07/2012 | BUILDING - FINAL | Denied | 1. PANELS AND RAILS ON ROOF LOOSE 2. GROUNDING ELECTRODE TO BE BONDED IN METAL RACEWAY 250.64 3. DISCONNECT WIRES ARE NOT LANDED. |
|
| 11/06/2012 | BUILDING - FINAL | Cancelled | IVRS - RI canceled |