Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/24/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/17/2012 ELECTRIC - FINAL Denied 1. BOXES TOO FAR BACK IN WALLS MORE THAN 1/4"
2. GROUNDED RECEPTABLE ON NON GROUNDED CIRCUITS
3. MISSING KITCHEN RECEPTICALES-NEED TO BE GFCI PROTECTION
4. MISSING WALL RECEPITCALES AND LIGHTS ALSO CEILING LIGHTS
5. USE APPROVED BOXES FOR LIGHTS AND FANS
6. NEED SMOKE DETECTORS IN BEDROOMS AND HALL INSTALL AS PER INSTRUCTIONS
7. FURNACE CORD IN DETERIOTED CONDITION
8.FILL USUSED OPENING IN BOTTOM OF PANEL
9. POOL EQUIPMENT MISSING PARTS
10. ROOF A/C WIRING NOT CODE COMPLAINT

+ NO POOL BARRIER FECE
+ ALL BATHROOMS AND KITCHEN PLUMBING MISSING
= PLEASE VERIFY PERMIT FOR NEW PLUMBING LINES