Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2013 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 02/27/2013 | PLUMBING - ROUGH, SOIL | Denied | INSTALL COMBO FITTINGS SAN TOOS ARE NOT LISTED FOR HORIZINTAL INSTALL PROVIDE APPROVED CLAMPS WIT ISOALTION ROM W 10' HAD TEST REQUIRED INDIRECT WASTE RECEPTABLES REQUEST READY ACCESS PLAN SPECS TYPE L.W | |
| 02/22/2013 | PLUMBING - ROUGH, SOIL | Denied | PLEASE READ COT FOOT SPA REQUIREMENTS HADOUT PROVIDED PROVIDE LISTING FOR SPAS LOWEWR ABS TO BELOW SLAB THEN WRAP WITH FOAM THE RISER THAT PENETRATES THE CONCERETE CAP OPEN THE TOILET AND SINK PIPES FOR SAFETY |
|
| 02/20/2013 | PLUMBING - ROUGH, SOIL | Denied | CONNECT NEW WASTE PIPE TO EXISTING WASTE PIPE NOT TO WC TRAP DRILL. PROVIDE APPROVED DRAINAGE FITTINGS PROPERLY INSTALLED TEST REQ |