Permit: T12CM05697

Parcel: 137055330

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/24/2012 ELECTRIC - INTERMEDIATE Approved EXAM ROOM 101 WALLS SHEETROCK OK 1 SIDE
09/20/2012 ELECTRIC - INTERMEDIATE Denied -USE APPROVED SUPPORTS FOR MC CABLE, 110-3 NEC
-CABLE MUST BE 1/4 BACK FROM FACE OF STUDS PER 300 NEC
-PLUG UN USED OPENING IN BOXES
- SUPPORT MC PER CODE 12" & 6'