Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2012 | BUILDING - FINAL | Denied | 1.LOOSE WIRE IN AC DISCONNECT 2. CABLE FOR SOLAR BREAKER MISSING DO NOT RELOCATE IN PANEL. 3. DC DISCONNECT AT INVERTER GROUNDING ELECTRODE ON WRONG LUG |