Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/12/2012 | ELECTRIC - RECONNECT | Denied | 1. WALL HEATER FAN CORD CANNOT PROTRUDE THROUGH A WALL TO PLUG INTO A KITCHEN OUTLET. 2. THE WEST SIDE SPOTLIGHT CIRCUIT WIRE WAS IMPROPERLY INSTALLED WITHOUT PROPER CONDUIT CONNECTIONS, AND THUSLY HAS DETERIORATED AND NEEDS REPLACEMENT OR REMOVAL. THIS CONDUIT ALSO NEEDS ITS OWN BREAKER AS PRESENTLY IT IS DOUBLE TAPPED. NOTE: IF THIS CIRCUIT IS REMOVED OR REPAIRED, THE HOLE IN THE SIDE OF THE ELEC PANEL MUST BE SEALED 3. POINTED SCREWS ARE NOT ALLOWED IN AN ELEC PANEL-IE IN KITCHEN PANEL |