Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM05670

Parcel: 113081060

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/17/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/12/2012 ELECTRIC - RECONNECT Denied 1. WALL HEATER FAN CORD CANNOT PROTRUDE THROUGH A WALL TO PLUG INTO A KITCHEN OUTLET.
2. THE WEST SIDE SPOTLIGHT CIRCUIT WIRE WAS IMPROPERLY INSTALLED WITHOUT PROPER CONDUIT CONNECTIONS, AND THUSLY HAS DETERIORATED AND NEEDS REPLACEMENT OR REMOVAL. THIS CONDUIT ALSO NEEDS ITS OWN BREAKER AS PRESENTLY IT IS DOUBLE TAPPED.
NOTE: IF THIS CIRCUIT IS REMOVED OR REPAIRED, THE HOLE IN THE SIDE OF THE ELEC PANEL MUST BE SEALED
3. POINTED SCREWS ARE NOT ALLOWED IN AN ELEC PANEL-IE IN KITCHEN PANEL