Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2012 | FIRE SPKLR - FINAL | Approved | ||
| 12/19/2012 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. still need to fix insulation in the shell portion of this permit still blocking sprinkler heads. | |
| 12/17/2012 | FIRE SPKLR - FINAL | Denied | 1. Correct upright coverage blocked by the insulation & one up right head in the kitchen area up against a 2x4 truss need to check all uprights. 2. Address numbers need to be posted on building and suite numbers posted 3. Have sub sprinkler contractor call in their sprinkler permits. 4. Have a annual sprinkler inspection done last report on file dated 2010 5. Rear exit in common area needs a exit sign over door and back up lighting. |