| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2012 | ELECTRIC - FINAL | Partial Approval | 1. SUPPORT M/C CABLE 330.17 & 30 2. JUCTION BOX OVERFILLED 314.16 3. CLOSE OPEN JUNCTION BOX & ANY UNUSED OPENINGS |