Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2015 | PLUMBING - MEDICAL GAS/FINAL | Approved | IVRS - Inspection :* | |
| 12/11/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/14/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | OK GAS FOR BLDG 1. PROVIDE INSTALL INSTRUCTIONS FOR WH'S BLDG 2 REQUIRES A RECONNECT PERMIT AND PIPING AND VENTING CORRECTION |
|
| 08/07/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/07/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | NFPA REQUIRES A MONITOR FOR PURGE GAS. KEEP TOOLS FREE FROM DIRT. CORRCT LEAKS. PERFORM ALL CONTRACTOR RQUIRED TESTS. SPECIAL INSPECTORS SHALL HAVE CITY APPROVAL | |
| 05/20/2015 | PLUMBING - MEDICAL GAS/FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/05/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/05/2015 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | TIE-IN PIPING INSPECTED BY SPECIAL INSPECTOR, PROVIDE REPORT. PROVIDE A PARTIAL REPORT FROM ENGINEER OF RECORD SHOWING COMPLIANCE W/ NEC 700.27 AS NOTED IN LOCKS/HOLDS/NOTICE |