Permit: T12CM05621

Parcel: 11012005A


Addresses:

2585 N WYATT DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T12CM05621

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2015 FRAMING Approved IVRS - Inspection :*
12/11/2015 FRAMING Not ready for Inspection IVRS - Inspection :*
08/15/2013 FRAMING Partial Approval IVRS - Inspection :*
08/15/2013 FRAMING Partial Approval PROVIDE A LETTER FROM ENGINEER TO USE WOOD FRAMING WHERE PLAN SHOWS METAL. INSPECTION ON NEW ENTRY
06/07/2013 FRAMING Partial Approval 1. This is a phased project. Do no final any inspection until all phases are complete. Walls at reception, and adjacent office OK electric in walls OK. West exam rooms/scheduling framing OK.
04/29/2013 FRAMING Partial Approval IVRS - Inspection :*
04/19/2013 FRAMING Denied 1. PLEASE VERIFY 03005 AND 0.3015 INSPECTIONS
2. SUPPORT SPLUMBING VETICALS IN WALLS PROTECT M/C INSIDE OF CHANNEL STUDS
STRAP M/C 12" OF BOX
WHERE ARE RECEPTACLES EXAM RM #6
CAN NOT USE DRYWALL SCREWS FOR STRUCTUAL ANCHORS TOP RAK