Permit: T12CM05598

Parcel: 13312068G

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/13/2013 FIRE - FINAL Approved
03/12/2013 FIRE - FINAL Partial Approval Remove ground wire from sprinkler piping on the open office area.
02/28/2013 FIRE - FINAL Denied Get insulation 1" off sprinkler head uprights throughout
Need to have sprinkler system monitored both tamper and flow
Sprinkler head in riser room taped needs cleaning
Label riser room door "RISER ROOM"
Remove ground wire from sprinkler piping - open office