Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM05598

Parcel: 13312068G

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
03/12/2013 FIRE - ALARM FINAL Approved
02/28/2013 FIRE - ALARM FINAL Denied Get insulation 1" off sprinkler head uprights throughout
Need to have sprinkler system monitored both tamper and flow
Sprinkler head in riser room taped needs cleaning
Label riser room door "RISER ROOM"
Remove ground wire from sprinkler piping - open office