Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2013 | FIRE - ALARM FINAL | Approved | ||
| 02/28/2013 | FIRE - ALARM FINAL | Denied | Get insulation 1" off sprinkler head uprights throughout Need to have sprinkler system monitored both tamper and flow Sprinkler head in riser room taped needs cleaning Label riser room door "RISER ROOM" Remove ground wire from sprinkler piping - open office |