Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2013 | FIRE SPKLR - FINAL | Approved | ||
| 03/12/2013 | FIRE SPKLR - FINAL | Partial Approval | Remove ground wire from sprinkler piping on the open office area. | |
| 02/28/2013 | FIRE SPKLR - FINAL | Denied | Get insulation 1" off sprinkler head uprights throughout Need to have sprinkler system monitored both tamper and flow Sprinkler head in riser room taped needs cleaning Label riser room door "RISER ROOM" Remove ground wire from sprinkler piping - open office |