Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2012 | MECHANICAL - FINAL | Partial Approval | a/c unit overfused gas flex not adequate for 116,000 btu & cannot exceed 3' support condensate drain every 4' paint exposed pvc with latex paint. use purple primer on all pvc fittings prior to glue. Support gas line Provise min r8 duct liner in supply on roof & rectangular supply duct on roof provide min 10 lb test on gas piping |