Permit: T12CM05530

Parcel: 114462540

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/15/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/09/2012 MECHANICAL - FINAL Partial Approval a/c unit overfused
gas flex not adequate for 116,000 btu & cannot exceed 3'
support condensate drain every 4' paint exposed pvc with latex paint. use purple primer on all pvc fittings prior to glue.
Support gas line
Provise min r8 duct liner in supply on roof & rectangular supply duct on roof
provide min 10 lb test on gas piping