Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/24/2012 | ELECTRIC - FINAL | Denied | 1. SPLICE FOR GFC TO BE IRREVERSIBLE TYPE: CRIMP OR CADWELL, NO SPLIT BOLT, PER 250 NEC 2. EXPOSED WIRING IN SHED, RECEPT TO BE GFI PER 210 NEZ |
|
| 09/05/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* -WIRING IN CARPORT NOT TO CODE-(ROMEX) -SERVICE GROUND WIRE CUT- REGROUND PER 250 NEC. -WIRING FOR LIGHTS IN BACK PORCH NOT TO CODE ALSO FOR DRYER IN LAUNDRY ROOM. -EXPOSED WIRING ABOVE GROUND BY BBQ- SHOULD BE 24" BELOW FRADE-TYPE OF CABLE PER 300-4.5 NEC. -PROVIDE ACCESS INTO SHED IN BACK YARD,ALSO HAS ELECTRICAL WIRING MAY BE HAZZARDOUS. USE LICENSED OR QUALIFIED ELECTRICIAN TO DO WORK AND RESCHEDULE A RE INSPECTION. |