Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/12/2012 | ELECTRIC - FINAL | Denied | A SMOKE DETECTOR IS REQUIRED IN THE DOWNSTAIR HALLWAY, ONE IN THE UPSTAIRS HALLWAY & ONE OUTSIDE OF BEDROOM IN THE APARTMENT AREA. THE J BX OUTSIDE IS STILL MISSING THE COVER PLATE. THE OUTDOOR RECEPTACLES STILL ARE NOT GFI PROTECTED. REPAIR THE BROKEN CONDUIT AT THE SOUTH CONDENSINGUNIT & SECURE TO THE WALL. THE NORTH CONDENSOR HAS EXPOSED WIRING & NOT CONNECTED PROPERLY TO CONDENSOR. SECURE CONDUIT TO WALL. THE BLACK CABLES CONNECTING TO THE CONDENSORS TO FAN COILS NEED TO BE IN CONDUIT & PROPERLY CONNECTED TO CONDENSORS. |
|
| 09/05/2012 | ELECTRIC - FINAL | Denied | A SMOKE DETECTOR IS REQUIREDIN THE UPSTAIRS HALLWAY, THE DOWNSTAIRS HALLWAY, & OUTSIDE OF THE MASTER BEDROOM. OUTDOOR RECEPTACLES MUST BE GFI PROTECTED. J BX AT PATIO MISSING COVER PLATE. NEED ACCESS TO CONDENSING UNITS ON SIDE OF HOUSE. THERE APPEARS TO BE EXPOSED WIRING AND POSSIBLY NO DISCONNECTS. GATE LOCKED. |